Atec Megger-TORKEL-820 Manuale Utente

Navigare online o scaricare Manuale Utente per Apparecchiature Atec Megger-TORKEL-820. Atec Megger-TORKEL-820 User Manual Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 6
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
TORKEL 820
Battery Load Unit
Batteries can be tested “in service”
Unit adjusts to include load currents in the
test parameters
User adjustable alarm and shutdown
points to avoid excessive discharge
Easily expandable for larger battery banks
using TXL extra load units
View test parameters/results “real time”
as testing progresses using TORKEL WIN
software
Easily save results to a PC for analysis,
report generation and storage
Description
During a power outage, crucial telecommunication and radio equip-
ment must be kept operating by batteries. However, the capacity of
such batteries can drop significantly for a number of reasons before
their calculated life expectancy is reached. Battery capacity should
thus be checked to prevent expensive downtime in the event of a
power failure.
The most reliable way to determine battery capacity is to conduct
a discharge test. The TORKEL™820 features a unique design that
combines efficiency with portability. Using TORKEL 820 you can
discharge 24 and 48 V batteries at a current of 270 A, and 12V
batteries at 135 A. Moreover, two or more TORKEL 820 units and/
or extra load units, TXL, can be linked together if you need higher
current. Discharging proceeds at constant current, constant power
or constant resistance, or in accordance with a pre-selected load
profile.
The TORKEL 820 issues a warning and/or shuts down the test
automatically when a) the voltage has dropped to a certain level,
b) discharging has continued through a certain time interval or c) a
certain amount of capacity has been dissipated.
TORKEL 820
Battery Load Unit
Application example
Testing can be carried out without disconnecting the battery from
the equipment it serves. Via a DC clamp-on ammeter, TORKEL820
measures total battery current while regulating it at a constant level.
The TORKEL 820 is connected to battery, the current and the volt-
age alarm level are set. After starting the discharge TORKEL820
keeps the current constant at the preset level. When the voltage
drops to a level slightly above the final voltage, TORKEL 820 issues
an alarm. The total voltage curve and the readings taken at the
end of the test are stored in TORKEL 820. Later, using the TORKEL
Win program, you can transfer these readings to your computer for
storage, printout or export. If your PC is connected to TORKEL 820
during the test, TORKEL Win builds up a voltage curve on the screen
in real time and displays the current, voltage and capacity readings.
You can also control the test using TORKEL Win.
Vedere la pagina 0
1 2 3 4 5 6

Sommario

Pagina 1 - TORKEL 820

TORKEL 820Battery Load Unit▪▪Batteries can be tested “in service”▪▪Unit adjusts to include load currents in the test parameters▪▪User adjustable alarm

Pagina 2 - TXL systems

TORKEL 820Battery Load Unit13121110931 42 5 6 7 8TORKEL and the extra load TXLFeatures and benefits1. Display2. External measurement input used to me

Pagina 3 - Specifications TORKEL 820

TORKEL 820Battery Load UnitSpecifications TORKEL 820Specifications are valid at nominal input voltage and an ambient temperature of +25°C, (77°F). Speci

Pagina 4 - Specifications TXL830 / 850

TORKEL 820Battery Load UnitSpecifications TXL830 / 850Specifications are valid at nominal input voltage and an ambient temperature of +25°C, (77°F). Sp

Pagina 5 - Additional equipment

TORKEL 820Battery Load UnitAdditional equipmentTORKEL Win▪Shows the complete voltage curve ▪Last recorded time, voltage, current and discharged capa

Pagina 6 - Included accessories

TORKEL 820Battery Load UnitSWEDENMegger Sweden AB Eldarvägen 4, Box 2970 SE-187 29 TÄBY T +46 8 510 195 00 F +46 8 510 195 95 E [email protected]

Commenti su questo manuale

Nessun commento